6kV to 30kV Aluminium Conductor XLPE Insulated PVC Sheathed Steel Tape Armored Three Cores Power Cable YJLV22

6kV to 30kV Aluminium Conductor XLPE Insulated PVC Sheathed Steel Tape Armored Three Cores Power Cable YJLV22


Construction:

Model: YJLV22;

Voltage: 3.6/6KV, 6/6KV, 6/10KV, 8.7/10KV, 8.7/15KV, 12/20KV, 18/20KV, 18/30KV;

Conductor: Aluminium Conductor;

Insulation: XLPE;

Inner Sheath: PVC;

Armor: Steel Tape Armor;

Outer Sheath: PVC.


Overview

Operation Characteristics:

XLPE insulation: the long-term allowable working temperature of conductor shall not exceed 90℃, and the maximum temperature of conductor shall not exceed 250℃ in case of short circuit(the longest duration shall not exceed 5 seconds)

Reference Outer Diameter and Approximate Weight of 6kV to 30kV Aluminium Conductor XLPE Insulated PVC Sheathed Steel Tape Armored Three Cores Power Cable YJLV22:

3.6/6 kV YJLV22
Number of cores × nominal cross-sectional area
(mm²)
Reference outer diameter
(mm)
Reference weight
(kg/km)
3×2538.8 972 
3×3541.1 2238 
3×5043.9 2536 
3×70  48.0 2979 
3×95  51.7 3439 
3×120  55.2 3913 
3×150  58.8 4439 
3×185  62.7 4952 
3x240  68.7 5991 
3×300  74.5 7003 
3×400  84.0 9190 
3×500  92.7 11146 



6/6kV and 6/10kV YJLV22
Number of cores × nominal cross-sectional area
(mm²)
Reference outer diameter
(mm)
Reference weight
(kg/km)
3×2543.1 2324 
3×3545.2 2557 
3×5048.4 2911 
3×7052.5 3387 
3×9556.0 3867 
3×12059.5 4342 
3×15062.9 4850 
3x18567.05473
3×24072.3 6435 
3×30077.5 7396 
3×40085.8 9403 
3×50093.6 11263 



8.7/10kV and 8.7/15kV YJLV22
Number of cores × nominal cross-sectional area
(mm²)
Reference outer diameter
(mm)
Reference weight
(kg/km)
3×2548.2 2740 
3×3550.6 3009 
3×5053.6 3370 
3×7057.3 3843 
3×9561.4 4408 
3×12064.8 4896 
3×15068.3 5492 
3×18572.1 6074 
3×24077.7 7088 
3×30084.0 8888 
3×40091.0 10259 
3×50099.0 12084 



12/20kV YJLV22
Number of cores × nominal cross-sectional area
(mm²)
Reference outer diameter
(mm)
Reference weight
(kg/km)
3×25  52.9 3195 
3×35  55.2 3492 
3×50  58.2 3841 
3×70  62.0 4340 
3×95  65.9 4894 
3×120  69.2 5460 
3×150  72.6 6015 
3×185  76.8 6662 
3×240  83.6 8518 
3×300  88.4 9537 
3×400  95.7 11001 
3×500  103.5 13103 



18/20kV and 18/30kV YJLV22
Number of cores × nominal cross-sectional area
(mm²)
Reference outer diameter
(mm)
Reference weight
(kg/km)
3×3567.8 4797 
3×5070.6 5323 
3×7074.5 5887 
3×9578.3 6521 
3×12083.2 7912 
3×15086.5 8608 
3×18590.6 9315 
3×24096.2 10513 
3×300101.0 11679 
3×400108.2 13203 
3×500116.1 5206 


Contact Us