60227 IEC 01(BV) Single-core Non-sheathed Cable with Rigid Conductor for General Purposes

60227 IEC 01(BV) Single-core Non-sheathed Cable with Rigid Conductor for General Purposes


Rated voltage: 450/750V;

Rated temperature: 70℃;

Conductor: 1.5-400mm², Class 1 or Class 2 conductor in GB/T 3956-2008;

Insulation: Lead free polyvinyl chloride (PVC/C-type polyvinyl chloride mixture).

Overview

Specification of 60227 IEC 01(BV) Cable:

Bending radius: When fixedly laid, the allowable bending radius for cables with an outer diameter (D) less than 25mm shall not be less than 4D, and for cables with an outer diameter (D) of 25mm or more, the allowable bending radius shall not be less than 6D;

Fixed installation temperature: -30℃ to +80℃;

Test voltage: 2500V;

Flame retardant: Complies with IEC 60332-1-2 standard and GB/T 18380.12-2008 standard;

Purpose: Used for electrical devices, instruments, telecommunications equipment, power lighting and other circuits with AC rated voltage of 450/750V or below or DC voltage of 1000V or below;

Installation methods: exposed laying, conduit laying, trunking laying, etc;

Standard: GB/T 5023.3-2008;

Certification: CCC certificate.

Technical Details of 60227 IEC 01(BV) Cable:

Conductor Nominal Cross Section Area
mm²
Conductor ClassInsulation Thickness Specified Value
mm
Average outside diameter
mm
Minimum Insulation Resistance at 70 ℃
(MΩ ·km)
Lower LimitUpper Limit
1.5 0.7 2.6 3.2 0.011 
1.5 0.7 2.7 3.3 0.010 
2.5 0.8 3.2 3.9 0.010 
2.5 0.8 3.3 4.0 0.009 
0.8 3.6 4.4 0.0085
0.8 3.8 4.6 0.0077
0.8 4.1 5.0 0.0070 
0.8 4.3 5.2 0.0065 
10 1.0 5.3 6.4 0.0070 
10 1.0 5.6 6.7 0.0065 
16 1.0 6.4 7.8 0.0050 
25 1.2 8.1 9.7 0.0050 
35 1.2 9.0 10.9 0.0043 
50 1.4 10.6 12.8 0.0043 
70 1.4 12.1 14.6 0.0035 
95 1.6 14.1 17.1 0.0035 
120 1.6 15.6 18.8 0.0032 
150 1.8 17.3 20.9 0.0032 
185 2.0 19.3 23.3 0.0032 
240 2.2 22.0 26.6 0.0032 
300 2.4 24.5 29.6 0.0030 
400 2.6 27.5 33.2 0.0028 


Contact Us